logo
salesjkt@flotech.co.id

iSOLV TDR Series

The measurement probe of the Time Domain Reflectometry (TDR) sensor ensures that the signal reaches the medium un-disturbed. High frequency microwave pulses travels along the detecting component steel rope or rod and reflects when reaching the product surface. The time from emission to re-ception is proportional to the distance between the surface and the reference plane on the instrument.

ENQUIRY
Request Price, Order and Brochure click here.
Features


• Can be used for medium with low conductivity
• Equipped with the advanced microprocessor and unique Echo Discovery processing technology
• Extremely low emission power
• Can be mounted on various metal or non-metal vessels
• Harmless towards the environment and human being
• Multiple options available in choosing various process connection and detecting component
• Despite disturbances such as agitator, or irregular surfaces, foam or coating of the probe, TDR will continue to provide reliable and accurate measurements
• Unaffected by changes in density and dielectric properties, dusts, vapor, and turbulence
• No moving parts

Application


Liquid
• Water & wastewater
• Chemical
• Petrochemical
• Food & beverages
• Pulp & Paper
• Oil & Gas


Bulk Solid
• Powder
• Fly ash
• Grain
• Cement
• Flour
• Sugar
• Coal dust

Specifications


TDR 100 Series— Rod Type
Version: TDR100SS / TDR100PTFE
Accuracy: ±5mm (Optional: ±2mm)
Process Connection: Threaded G1½A / G2A / 1½NPT
Process Connection Material: Flange : DN50 / DN80 / DN100 / DN150
Detection Component Material: Stainless Steel SS316L / PTFE
Length of Rod: 500mm to 6000mm
Process Pressure: (-0.1 to 4 )MPa
Process Temperature: (-30 to 150) Deg C
Signal Output: (4 to 20) mA / HART
Housing/Protection: Aluminum/ Stainless Steel / Plastic
Power: 2-Wire (DC 24V), 4-Wire (DC 24V / AC220V)
Explosion Proof Approval: Intrinsically Safe (Exia IIC T6) - for 2 Wire Loop System Only Explosion Proof (Exd IIC T6)
Cable Entry: M20 x 1.5 / ½ NPT
Protection Class: IP67

TDR 200 Series— Flexible Cable Type
Version: TDR200
Accuracy: ±5mm (Optional: ±2mm)
Process Connection: Threaded : G1½A / G2A / 1½NPT
Process Connection Material: SS316L
Detection Component Material: Stainless Steel 316L
Length of Flexible Cable: 1000mm to 30000mm
Process Pressure: (-0.1 to 4 )MPa
Process Temperature: (-30 to 150) Deg C
Signal Output: (4 to 20) mA / HART
Housing/Protection: Aluminum/ Stainless Steel / Plastic
Power: 2-Wire (DC 24V), 4-Wire (DC 24V / AC220V)
Explosion Proof Approval: Intrinsically Safe (Exia IIC T6) - for 2 Wire Loop System Only Explosion Proof (Exd IIC T6)
Cable Entry: M20 x 1.5 / ½ NPT
Protection Class: IP67
Display: Dot matrix display / text indication with graphic support (optional)