logo
salesjkt@flotech.co.id

iSOLV BTU Measurement


iSOLV BTU Measurement System is used to measure individual energy consumption in any liquid heating/cooling systems. This system is also used to measure performance of energy saving system or the loss of efficiency which is directly tied to loss of revenue.

The iSOLV BTU Measurement System is supplied complete with electromagnetic flowmeter and temperature probes. The system real-time detects the temperature of supply and return pipe. It also monitors the instantaneous flow rate according to Heat Exchange of Thermodynamics principle. The iSOLV BTU meter automatically integrates energy consumption and transfers it to the computer. The consumption volume can be checked by a tenant or operator with no worries. It provides real time information such as instantaneous temperature, flow rate, energy consumption, and others.

Application reference:


ENQUIRY
Request Price, Order and Brochure click here.
Features

• Complies with OIML R75 and EN1434 standards.
• Real time display of supply / return water temperature, instantaneous flow rate, cooling consumption value, heating consumption value, instantaneous power, total flow rate etc.
• Four different units of measurements available: MJ, GJ, kWh/h, MWh/h
• Password protection available.
• RS485 Communication protocol.
• Matched pair of 3-wire Temperature sensor PT1000, for higher resolution and better accuracy

Application

• BTU meters measure the energy content of liquid flow in British thermal units (BTU), a basic measure of thermal energy.
• BTU meters are used in chilled water systems for both commercial and industrial and office buildings. These meters are used to bill users for energy usage.

Specifications

BTU METER
Operating voltage: 220VAC±10% ,50±1Hz
Temperature range: (0.0~99.9)℃
Temperature accuracy: ±0.1℃
Matched with temperature sensor: PT1000
Flow rate range: (0~9999.99)m/h
Flow rate accuracy: ±1.5%
Matched with flow rate sensor: Pulse mode or Current mode
Flow rate signal range: Pulse mode 0~200Hz & Current mode 4-20mA
Cooling consumption accumulated range: (0~999999.999999)MWh
Heating consumption accumulated range: (0~999999.999999)MWh
Resolution ratio: 0.000001 MWh
Energy accumulated accuracy: ClassⅡ
Communication interface: RS-485
Communication rate: 9600bps
Max. communication distance: 400m
Dimension: 250mm×150mm×60mm

TEMPERATURE SENSORS
Type: 3-wire PT1000 Temperature sensors
Location: 1 x Supply Line and 1 x Return Line
Complete with: Thermowell and Socket Weld

FLOW SENSOR EFS802
Performance full bore electromagnetic Flowmeter
Accuracy: +/- 0.5%
Repeatability: +/- 0.1%
Full Scale Range Setting: 0.3 m/s to 15 m/s
Fluid Conductivity: > 5μS/cm
Fluid Temperature: -25°C to 90°C
Ambient Temperature: -40°C to 65°C
Calibration Certificate Wet Calibration: – 3 Points (Additional Test Points Upon Request)

Sensor Model EFS802
Process Connection: Size DN15-DN1000
Type Flange: DIN 2501/ ANSI/JIS
Pressure Rating Refer To Page 8. Higher Pressure Rating Available On Request
Material Tube: SS304
Liner (Wetted Parts): Hard Rubber (Std) / PTFE/ Others On Request
Signal Electrode (Wetted Parts): SS316 (Std)/ Hastelloy C/ Tantalum/ Titanium
Process - Flange: Carbon Steel (Std)/ SS304 (Optional With Price Adder)
Housing Steel: With Epoxy Paint
Grounding Rings: SS304 / SS316 (Optional)
Flow Direction: Bi-directional (Forward / Reverse)
Protection Class: IP 68

Transmitter Model RFT202
Operating Voltage: 85 - 250 VAC, 45 - 63Hz
Temperature Range: 0 - 199.9 °C
Matched with Temperature Sensor: PT1000
Flow Rate Range: (0 - 99999)m³/h
Cooling Consumption Accumulated Range: (0 – 999999999)m³
Heating Consumption Accumulated Range: (0 – 999999999)m³
Communication Interface: RS-485
Communication Rate: 300 - 38400 bps
Dimension: 214 mm x 164 mm x 71 mm
System Accuracy (Including flowmeter, temperature sensors): < +/-2%

FLOTECH CONTROLS INDONESIA
Jl. Boulevard Artha Gading - Artha Gading Niaga
Blok F/7, Kelapa Gading - Jakarta 14240 Indonesia
Telp: +62 21 45850778 / Fax: +62 21 45850779
Copyright © 2017 - PT Flotech Controls Indonesia || All Rights Reserved